Calculate infiltration heat gain using ACH, CFM, air density, humidity ratio, and enthalpy inputs accurately. Size cooling loads with clearer confidence across demanding projects.
The page uses one main column, while the form below switches to three columns on large screens, two on small screens, and one on mobile.
Volume = Length × Width × Height
CFM = (ACH × Volume) ÷ 60
W = 0.62198 × Pv ÷ (P − Pv)
Pv is vapor pressure. P is barometric pressure. The page estimates vapor pressure from dry-bulb temperature and RH.
h = 0.24T + W(1061 + 0.444T)
T is in °F. h is in Btu per pound of dry air.
Total Load = ṁdry air × (hout − hin)
Sensible Load = ṁdry air × 0.24 × (Tout − Tin)
Latent Load = Total Load − Sensible Load
| Project Type | Space Size | Ceiling Height | ACH / CFM Basis | Indoor Condition | Outdoor Condition | Typical Use Note |
|---|---|---|---|---|---|---|
| Small office | 1,200 ft² | 10 ft | 0.35 ACH | 75°F / 50% RH | 92°F / 60% RH | Light envelope leakage and normal occupancy. |
| Retail entry zone | 2,000 ft² | 12 ft | 650 CFM | 74°F / 50% RH | 95°F / 65% RH | Frequent door opening increases infiltration. |
| Warehouse support room | 3,600 ft² | 16 ft | 0.80 ACH | 78°F / 55% RH | 100°F / 55% RH | Dock traffic and pressure imbalance matter. |
| Lobby with vestibule | 1,500 ft² | 14 ft | 0.50 ACH | 75°F / 50% RH | 90°F / 70% RH | Vestibule reduces direct outdoor mixing. |
It is the cooling load caused when unwanted outdoor air leaks into a conditioned building. That incoming air changes room temperature and moisture content, increasing equipment load.
Use ACH when leakage is estimated from building size and air change assumptions. Use direct CFM when blower-door, balancing, or field measurements already provide airflow.
Sensible load reflects temperature change. Latent load reflects moisture added or removed. Both matter because cooling equipment must handle dry-bulb control and humidity control together.
Pressure changes air density. Density changes mass flow, and mass flow changes heat transfer. This matters more at high elevations or unusual weather conditions.
Yes. If outdoor air is cooler or less energetic than indoor air, infiltration can reduce cooling demand. The tool still reports the signed value so you can see relief instead of gain.
It scales the base infiltration airflow. Use it to represent door opening frequency, envelope quality, pressure imbalance, or conservative design adjustments during early estimating.
A safety factor increases design airflow beyond the raw estimate. It helps account for uncertainty, future operation changes, and incomplete field information during preliminary sizing.
It is useful for advanced estimating and quick checks. Final design should still confirm envelope leakage, psychrometric assumptions, schedules, and code requirements with project-specific engineering review.
Important Note: All the Calculators listed in this site are for educational purpose only and we do not guarentee the accuracy of results. Please do consult with other sources as well.